JKWF Series controller regards 8 single-chip microcomputer as core, adopt the control scheme of phase splitting sampling and compensation and common compensation and phase splitting compensated altogether, very suitable for reactive compensation with 50Hz, 0.4KV three-phase load imbalance power system.
Technical data
Basic Parameter
Rated voltage: AC 220V±10% Rated current: AC 0-5A Rated frequency: 50Hz±5%
Control Parameter
Sensitivity: 100mA
COS φ Preset: 0.80-0.99; step length 0.01; Factory preset 0.98 input and cutoff time
Delay: dynamic state 100ms-30S; Static state 1-250S;Factory preset dynamic state 5S; static state 30S.
Capacitance capacity: 0-99kvar factor preset of each branch 10kvar
Contact capacity: dynamic state output of each branch DC12V×50mA
Static state output of each branch 380V×7A/200V×5A
Measuring accuracy
Voltage: ±0.5% Current: ±0.5% Power factor: ±1.0%
Active power: ±1.0%
Reactive power: ±1.0%
Function characteristic
Liquid crystal display or LED shows three-phase voltage, current, active power, reactive power, power, power, power factor and power network frequency, control parameter, etc..(utilize this series of continue rollers to assemble the capacitance case or compensator can save ampere meter, voltmeter, universal change-over switch, etc.)
Strong anti-interference ability can resist 2000V interference pulse from power direct, and not crashing, does not lose the data, it is reliable to run steady.
Reactive power control physical quantity, high control precision;
The user can revise the control parameter according to his own need, the control parameter is not lost to have a power failure.
With automatic discriminating phase function(sampling signal automatic be kept in the same state).
The input resistance of current sampling signal is smaller than 0.05Ω; it can be taken out from measuring loops directly.
With over-voltage, under-voltage, imperfect phase protective function.
Compensation mode: phase splitting compensation, phase splitting slipping compensation and
three-phase compensation, the three-phase compensation.
Output mode: static state, dynamic state, compound etc.